You are here: Home - UPS On-line single phaseInverter - in UPS operating - ORVALDI VR6-10K on-line

series: UPS On-line single phaseInverter - in UPS operating

ORVALDI VR6-10K on-line

Expansive Power, Seamless Integration. ORVALDI VR6-10K on-line has a compact 2U design, perfect for scalable setups requiring parallel capability.

PRODUCT FEATURES:   

  • True Double-Conversion: Ensures reliable protection for sensitive devices.
  • Power Factor: Output power factor of 1 for optimal efficiency.
  • Wide Voltage Range: Operates with 110-300 V AC.
  • User-Friendly: LCD panel for easy monitoring.
  • Design: Rack/Tower convertible design.
  • Power Factor Correction: Input power factor of 0.99.
  • ECO Mode: Energy-saving operation.
  • Communication: USB and RS-232, with optional SNMP and AS400 relay cards.
  • Parallel Operation: Supports parallel operation of up to 3 units for 30kW total capacity.

LIST OF APPLICATIONS:

  • Household electronics
  • Emergency lighting
  • Alarm systems
  • Telecommunications equipment
  • Fiscal devices
  • Servers and small networks (passive PFC)
  • Medical equipment
  • Critical loads in data centers

"HIGH QUALITY" OPTION:

ORVALDI will, in accordance with the terms and conditions of insurance, replace, repair or compensate ORVALDI products and/or connected devices in the event of damage as a result of an electrical surge. The maximum total amount compensated is 5000Euro (five thousand Euros).

Topology

True double-conversion provides continuous and stable power, ideal for high-demand environments.

Display

Easy-to-read LCD interface for immediate access to system status, load levels, and operational settings.

ORVALDI VR6-10K

Flexible connectivity options with hardwire terminal blocks to accommodate various installation needs.

Battery Management

Designed for optional external battery packs, allowing for extended runtime configurations.

Communication

Includes USB and RS-232 ports, with optional SNMP and relay cards for comprehensive system integration.

Efficiency Modes

ECO mode available to minimize power consumption while maintaining critical operations.

Parallel Configuration

Built-in capability for parallel operation up to three units, scaling up to 30kW to support growing power needs.

TECHNICAL DATA:
Model ORVALDI VR6K on-line 2U LCD ORVALDI VR10K on-line 2U LCD
Part No VGAR6K VGAR10K
Maximum Power 6000VA / 6000W 10000VA / 10000W
Input
Input Voltage 110-300VAC at 0-60% load
140-300VAC at 60-80% load
176-300VAC at 80-100% load
Input Frequency 46~54Hz or 56~64Hz
Power Factor >0.99 at 100% load
Output
Output Voltage 208, 220, 230, 240VAC (user-programmable)
Output Frequency (Battery Mode) 50Hz ± 0.1Hz or 60Hz ± 0.1Hz
Crest Factor 3:1
Harmonic Distortion ≦ 1% at linear load, ≦ 4% at non-linear load (100% load)
Transfer Time 0 ms (below 10ms in ECO mode)
Output Waveform Pure Sine Wave
Efficiency (AC Mode) 94%
Efficiency (Battery Mode) 93%
Batteries
Type and Quantity 16-20 pcs, capacity depends on desired battery runtime
Charging Voltage (Float) 218.4VDC ± 1% for 16 batteries
Charging Current 4A
LCD Display Information Operating mode, load level, battery charge level, input/output voltage, battery runtime, warnings, and errors.
Alarms
Battery Mode Beep every 4 seconds
Low Battery Beep every second
Overload Two beeps per second
Fault Continuous beeping
Dimensions
External [mm] 438 x 88 x 600
Weight [kg] 17 20
Environment
Temperature and Humidity 0-95% (non-condensing), 0-40°C (battery life shortens at operating temperatures above 25°C)
Noise Level below 55dB at 1m
Communication
USB/RS232 Standard
SNMP/AS400 Optional

Lorem ipsum dolor sit amet, consectetur adipiscing elit. Sed iaculis suscipit felis non sagittis. Proin vel sodales quam. Fusce quis mollis purus. Aenean quis est lorem. Etiam elementum luctus arcu, eget pretium dui vehicula sed. Maecenas quis tortor nibh. Quisque lorem ex, lobortis eget vulputate ac, vestibulum euismod sapien.